28 Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
Chapter 2 Set Up in the Studio 5000 Logix Designer Application
Master Configuration
1. Open the master configuration page from the config tree to access the
linking device master configuration settings.
2. Choose the Topology for the master linking device.
3. Enter the configuration values.
4. Click the Download Config button to download the settings to the
linking device.
The settings are stored in nonvolatile memory in the linking device.
5. Click the Apply button to store the configuration in the project file.
To p ol o g y
Choose the correct Topology mode for the application. The graphical
representation must be used to match the topology. See Appendix D
for available
options. Use this setting to configure redundant linking devices, redundant H1
media, and the internal H1 segment terminators.
FF Master Node
The H1 Master (linking device) needs a node number to operate on the H1
network. The default is node number 16 (0x10).
Do not modify the default node number; doing so can result in loss of
communication.