62 Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
Appendix A Linking Device Display Status
H1 Master Page
The next page that is accessed by the
Page button is the H1 Master page.
Bus A/B: Displays the bus voltages,
currents, and bus status.
Temp e r a t ur e : Displays the internal
temperature of the linking device.
External Pwr: Displays the power
supply voltage.
FF Node: Displays the H1 node
address for the master (default 16).
BusA/B Enabled: H1 Bus A or H1 Bus B is enabled for communication.
BusA/B Tripped: H1 Bus A or H1 Bus B has tripped indicating that there was
an over-current on either port.
BusA/B Term: The linking device is configured to terminate H1 Bus A or H1
Bus B.
Field Device Page
The next 16 FF Field Device pages
display the status of each of the field
device indices.
FF Node: Displays the H1 node
address.
Device Tag Name: The tag name of
the device.
Status: Displays the field device status
(see Ta bl e 9
.)
Table 9 - Field Device Status
Success: Displays the data packets that are received as a percentage of packets
that are sent for the previous 100 packets.
Pckt Send: Displays the total number of data packets that are sent from the field
device.
Status Description
Not Connected Device cannot be seen
Online Online - not configured
ConfigRunning Device is configured and
running