Rockwell Automation Publication 1788-UM057B-EN-P - September 2014 77
Field Device Block Configuration Examples Appendix C
21. Set the value of the controller tag that is associated with the quality of
CAS_IN (connector PV:O.1) status parameter (PVx_GoodCascade) to
the value 1.
22. Verify that the NotInvited status has been replaced by the new status,
InitializationRequest.
The InitializationRequested must receive a response.
23. Set the value of the Controller Tag associated with the substatus of
CAS_IN (connector PV:O.1) status parameter (PV1_SubStatus) to the
value 1, which is InitializationAcknowledge.