1794 FLEX I/O Diagnostic Digital Modules Overview 15
Capabilities of the 1794-IB16D include:
61131-2 Type 3 compatible sinking inputs.
interface with PNP sourcing sensors.
10-31.2V dc operating range.
provides up to 50 mA to power an attached sensor.
detects for an open wire condition down to 50 μA.
You need a dummy resistor to mask the channel diagnostic function for each
unused sensor port. Used sensor ports must have a 50 μA minimum current
draw with the input field device in both the on- and off-state.
1794-OB16D Diagnostic Output Module Compatibility
You can use FLEX I/O diagnostic output modules to drive a variety of output
devices. Typical output devices include the following.
•Relays
Solenoids
Contactors
Indicators
Small motor starters
When you design a system using FLEX I/O diagnostic output modules, you
must consider:
The output must supply the necessary surge and continuous current for
the output device being used.
When sizing output loads, check the documentation supplied with the
output device for the surge and continuous current needed to operate
the device.
Capabilities of the 1794-OB16D diagnostic output module include:
sourcing style outputs for loads connected to common.
10-31.2V dc operating range.
provides continuous current of 0.5 A maximum (8 A per module),
2.0 mA minimum per output.
capable of 2 A surge for 50 ms, repeatable every 2 s.
protection from short circuit and overload.
You need a dummy resistor to mask the channel diagnostic function for each
unused output channel.