4-4 Using BACnet Objects
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object Name Use This Object to…
Compatible PowerFlex Drives
70 Std. 70 EC 700 Std. 700 VC 700 H
AV4 Output Voltage (VAC) Read the drive’s output voltage. ✔✔ ✔ ✔✔
AV5 Output Power (kW) Read the drive’s output power. ✔✔ ✔ ✔✔
AV6 Output Energy (kWh) Read/write the drive’s accumulated output energy.
Note: When writing, this object accepts only a value of “0” (zero).
✔✔ ✔ ✔✔
AV7 DC Bus Voltage (VDC) Read the drive’s DC bus voltage. ✔✔ ✔ ✔✔
AV8 Drive Temp (°C) Read the drive’s temperature. ✔✔ ✔ ✔✔
AV9 PID Feedback (%) Read the drive’s PID feedback. ✔✔ ✔ ✔✔
AV10 PID Error (%) Read the drive’s PID error. ✔✔ ✔ ✔✔
AV11 Run Time (Hours) Read/write the drive’s accumulated run time.
Note: When writing, this object accepts only a value of “0” (zero).
✔✔ ✔ ✔✔
AV12 Fault 1 Read the code for the drive’s most recent fault. ✔✔ ✔ ✔✔
AV13 Fault 2 Read the code for the drive’s second most recent fault. ✔✔ ✔ ✔✔
AV14 Fault 3 Read the code for the drive’s third most recent fault. ✔✔ ✔ ✔✔
AV15 Accel Time 1 (Sec) Read/write the drive’s Accel Time 1 setting. ✔✔ ✔ ✔✔
AV16 Decel Time 1 (Sec) Read/write the drive’s Decel Time 1 setting. ✔✔ ✔ ✔✔
AV17 Mailbox Param Read/write any drive parameter. To read a drive parameter, write the
number for the desired parameter to the Mailbox Param object, and
then read the Mailbox Value object. To write a drive parameter, write
the number for the desired parameter to the Mailbox Param object,
and then write the desired value to the Mailbox Value object.
✔✔ ✔ ✔✔
AV18 Mailbox Value ✔✔ ✔ ✔✔
Binary Input (BI) Objects
BI0 Digital Input 1 Read the state of Digital Input 1 on the drive’s I/O terminal block. ✔✔ ✔ ✔✔
BI1 Digital Input 2 Read the state of Digital Input 2 on the drive’s I/O terminal block. ✔✔ ✔ ✔✔
BI2 Digital Input 3 Read the state of Digital Input 3 on the drive’s I/O terminal block. ✔✔ ✔ ✔✔