Troubleshooting 5-3
MOD Status Indicator
State Cause Corrective Actions
Off The adapter is not powered or
is not properly connected to
the drive.
Securely connect the adapter to the drive
using the Internal Interface (ribbon)
cable.
Apply power to the drive (or adapter if
mounted in a DPI External Comms Kit).
Flashing
Red
The adapter has failed the
firmware test.
Cycle power to the drive (or adapter if
mounted in a DPI External Comms Kit).
If cycling power does not correct the
problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.
If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
Flashing
Green
The adapter is operational, but
is not transferring I/O data.
Enable the network device that is providing
control to the adapter.
Solid Green The adapter is operational and
transferring I/O data.
No action required.