Adapter Parameters B-3
07 [Baud Rate Act]
Displays the baud rate (kilobits per second)
actually used by the adapter.
Default: 0 = Unknown
Values: 0 = Unknown
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps
Type: Read Only
08 [MAC Address]
Displays the actual address selected by the MAC
Address Switches SW1-SW7 (Figure 2.1
) on the
adapter. This value is latched when the adapter
powers up.
Default: 0
Minimum: 0
Maximum: 127
Type: Read Only
09 [Max Master]
Sets the maximum MAC Address for any device in
the BACnet MS/TP token ring.
Default: 127
Minimum: 0
Maximum: 127
Type: Read/Write
Reset Required: Yes
10 [Max Info Frames]
Sets the maximum number of messages that the
adapter can transmit while it owns the token.
Default: 1
Minimum: 1
Maximum: 255
Type: Read/Write
Reset Required: Yes
11 [Device Instance]
Sets the Device Instance Number used by the
adapter.
Default: 160000
Minimum: 0
Maximum: 4194302
Type: Read/Write
Reset Required: Yes