Appendix B
Adapter Parameters
Appendix B provides information about the BACnet MS/TP adapter
parameters.
The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.
Topic Page
About Parameter Numbers
B-1
Parameter List B-1
About Parameter Numbers
Configuration Tool Numbering Scheme
• DriveExplorer
• DriveExecutive
• HIM
The adapter parameters begin with parameter 1. For
example, Parameter 01 - [Reset Module] is parameter
1 as indicated by this manual.
Parameter List
Parameter
No. Name and Description Details
01 [Reset Module]
No action if set to “Ready.” Resets the adapter if
set to “Reset Module.” Restores the adapter to its
factory default settings if set to “Set Defaults.” This
parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.
Default: 0 = Ready
Values 0 = Ready
1 = Reset Module
2 = Set Defaults
Type: Read/Write
Reset Required: No
!
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.