Using BACnet Objects 4-5
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object Name Use This Object to…
Compatible PowerFlex Drives
70 Std. 70 EC 700 Std. 700 VC 700 H
BI3 Digital Input 4 Read the state of Digital Input 4 on the drive’s I/O terminal block. ✔✔ ✔✔
BI4 Digital Input 5 Read the state of Digital Input 5 on the drive’s I/O terminal block. ✔✔ ✔✔
BI5 Digital Input 6 Read the state of Digital Input 6 on the drive’s I/O terminal block. ✔✔ ✔✔
BI10 Digital Output Act 1 Read the state of Digital Output 1 on the drive’s I/O terminal block. ✔✔ ✔✔
BI11 Digital Output Act 2 Read the state of Digital Output 2 on the drive’s I/O terminal block. ✔✔ ✔✔
BI12 Digital Output Act 3 Read the state of Digital Output 3 on the drive’s I/O terminal block. ✔✔
Binary Output (BO) Objects
BO0 Digital Output Cmd 1 Read/write the state of Digital Output 1 on the drive’s I/O terminal
block. The drive must be configured to accept the value of this output
from the network. This is done by setting drive parameter 380 - [Digital
Out1 Sel] to the value “30” (Param Cntl).
✔✔
BO1 Digital Output Cmd 2 Read/write the state of Digital Output 2 on the drive’s I/O terminal
block. The drive must be configured to accept the value of this output
from the network. This is done by setting drive parameter 384 - [Digital
Out2 Sel] to the value “30” (Param Cntl).
✔✔
BO2 Digital Output Cmd 3 Read/write the state of Digital Output 3 on the drive’s I/O terminal
block. The drive must be configured to accept the value of this output
from the network. This is done by setting drive parameter 388 - [Digital
Out3 Sel] to the value “30” (Param Cntl).
—— ✔✔
Binary Value (BV) Objects
BV0 Ready Read the drive’s Ready status, which is active if the drive is ready to
accept a run command.
✔✔ ✔✔
BV1 Running Read the drive’s Running status, which is active if the drive is running. ✔✔ ✔✔