Rockwell-automation 20-COMM-R Remote I/O Adapter Manual de usuario Pagina 64

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 128
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 63
5-6 Using Block Transfer Messaging
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
The following table describes the main events and what a program is
monitoring when performing Block Transfer messaging.
3. Receive data from the program.
After the program with Block Transfer messages has been run, the
results can be seen in a data file. The data file that is used depends on
your controller and application.
Example Programs
The example ladder logic programs (Figure 5.3, Figure 5.4, and Figure 5.6)
can be used to demonstrate how Block Transfer can be used to send Explicit
Messages from a ControlLogix, PLC or SLC controller, respectively. With
these examples, Block Transfer messaging is used to read or write a
parameter value from a PowerFlex 70 drive at Rack 1, Group 0, Slot 0.
These example ladder programs are continuations of the Discrete and Block
Transfer I/O example ladder programs in Chapter
4. The ‘Main Routine’
ladder logic in that chapter performs Jump to Subroutines (JSRs) to these
examples.
Item Event Description
BTW Request Before initiating a Block Transfer message, bit 8 must be 1. This
setting indicates that the adapter and drive are communicating, so
a Block Transfer message will reach the drive.
Before initiating a Block Transfer Write message, bit 9 must be 1.
This setting indicates that a Block Transfer Write can be executed.
BTW Data at
Adapter
Because only one Block Transfer message can be active at a time,
bit 9 is set to 0 when the Block Transfer Write begins. Bit 9 and bit
10 remain at zero while the Block Transfer is being processed.
BTW Complete When the Block Transfer is complete, bit 9 and bit 10 are set to 1.
This setting indicates that the program can perform either a Block
Transfer Read or a Block Transfer Write.
Bit 11 remains at 0 if messaging is successful. If an error occurs, it
would be set to 1.
BTR Request Before initiating a Block Transfer Read message, bit 10 must be set
to 1. This setting indicates that data is available to read. When the
message is executed, bit 9 and bit 10 are set to 0 because only
one Block Transfer can be active at a time.
Vista de pagina 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 127 128

Comentarios a estos manuales

Sin comentarios