C-8 CIP Objects
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
Formulas for Converting
Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10
Decimal Places
)
Internal Value = ((Display Value x Divisor x 10
Decimal Places
) / (Multiplier x Base)) - Offset
Object-Specific Services
Service Code Implemented for: Service Name Allocation Size (in bytes)
Class Instance Par. Number Par. Value
0x4B
(1)
(1)
Must be directed to Instance 0 and Attribute 0.
Yes No Get_Attributes_Scattered 2 2
0x4C
(1)
Yes No Set_Attributes_Scattered 2 2
0x4D
(2)
(2)
These services are supported only when the adapter is used with a PowerFlex 750-Series drive.
Yes No Get_Attributes_Scattered 4 4
0x4E
(2)
Yes No Set_Attributes_Scattered 4 4