Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013 125
Figure 28 Typical V/Hz Curve for Full Custom (with Speed/Frequency Limits
Owners An owner is a parameter that contains one bit for each of the possible DPI or
SCANport adapters. The bits are set high (value of 1) when its adapter is
currently issuing that command, and set low when its adapter is not issuing that
command. Ownership falls into two categories;
Exclusive
Only one adapter at a time can issue the command and only one bit in the
parameter will be high.
For example, it is not allowable to have one Adapter command the drive to run in
the forward direction while another Adapter is issuing a command to make the
drive run in reverse. Direction Control, therefore, is exclusive ownership.
Frequency
Output Voltage
Overspeed
Limit
Frequency Trim
due to Speed
Control Mode
Maximum
Voltage
Motor NP
Voltage
Run
Boost
Break
Voltage
Start
Boost
Allowable Output Frequency Range - Normal Operation
Allowable Speed Reference Range
Allowable Output Frequency Range -
Bus Regulation or Current Limit
Maximum
Frequency
Motor NP Hz0 Break
Frequency
Maximum
Speed
Minimum
Speed
Output
Frequency
Limit
(lower limit on this range can be 0 depending on the value of Speed Adder)