Analog Outputs
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013 31
Here, the deadband is “shifted” due to the 50 Hz limitation. The command
frequency from 0 to 3 volts on the analog input will be 15 Hz. After 3 volts, the
frequency will increase at a rate of 0.2 volts per hertz up to 9 volts. After 9 volts
on the analog input the frequency command will remain at 45 Hz.
Analog Outputs Explanation
Each drive has one or more analog outputs that can be used to annunciate a wide
variety of drive operating conditions and values.
The user selects the analog output source by setting [Analog Out Sel].
Configuration
The PowerFlex 70 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 7 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.
The PowerFlex 700 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 100 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.
INPUTS & OUTPUTS
Analog Outputs
342
345
[Analog Out1 Sel]
[Analog Out2 Sel]
Selects the source of the value that drives the analog
output.
Default:
Options:
0“Output Freq
See Table
001
002
003
004
005
007
006
012
135
136
137
138
220
219
377
378
Vector
* Vector Control Option Only **Vector firmware 3.001 & later
(1)
Refer to Option Definitions in User Manual.
Options
[Analog Out1 Lo] Value
[Analog Out1 Hi] Value
Param. 341 = Signed Param. 341 = Absolute
0
1
1*
2
3
4
5
6
7
8
9
10
11
12
13
14*
15*
16*
17*
18*
19*
20-23**
24**
“Output Freq”
“Command Freq”
“Command Spd”
“Output Amps
“Torque Amps
“Flux Amps
“Output Power”
“Output Volts
“DC Bus Volts
“PI Reference”
(1)
“PI Feedback”
“PI Error”
“PI Output”
“%Motor OL
“%Drive OL
“CommandedTrq”
“MtrTrqCurRef
(1)
“Speed Ref
“Speed Fdbk”
“Pulse In Ref”
(1)
“Torque Est”
(1)
“Scale Block1-4”
(1)
“Param Cntl”
(1)
–[Maximum Speed]
–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
800% Rated
–200% Rated
–[Maximum Speed]
–[Maximum Speed]
–25200.0 RPM
800%
0 Hz
0 Hz
0 Hz/RPM
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
0%
0%
0 Hz/RPM
0 Hz/RPM
0 Hz/RPM
0%
+[Maximum Speed]
+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% R
ated
120% Rated Input Volts
200% Rated Input Volts
100%
100%
100%
100%
100%
100%
800% Rated
200% Rated
+[Maximum Speed]
+[Maximum Speed]
+[Maximum Speed]
+800%