Stop Modes
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013 199
5. Ramp To Hold is selected by setting [Stop Select x]. The drive will ramp the
frequency to zero based on the deceleration time programmed into [Decel
Time 1/2]. Once the drive reaches zero hertz, a DC Injection holding current
is applied to the motor. The level of current is set in [DC Brake Level].
In this mode, the braking is applied Continuously. [DC Hold Time] has no
effect in this mode. Braking will continue until one of the following events
occur:
–The Enable Input is opened, or . . .
A Start command is re-issued.
Again, caution must be exercised to not overheat the motor by applying excess
voltage and/or for excess time, particularly if the motor is not rotating.
DC
Hold Level
Time
Output Voltage
Output Voltage
Output Current
Output Current
Motor Speed
Output Voltage
Output Current
Motor Speed
Re-issuing a
Start Command
Stop
Command
Zero
Command
Speed