Rockwell-automation 2705 RediSTATION Operator Interface User Manual Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
Publication 2705-UM001A-EN-P
Installation and Mounting 2-5
Setting the Output Flash Rate
DIP switch 10 sets the flash rate of the outputs (pilot lights). The
factory default setting is 1 Hz.
To change the flash rate, slide switch 10 to the appropriate ON/OFF
position.
DeviceNet Termination
Devices on end nodes of the DeviceNet network require termination.
If the RediSTATION is an end node, you must provide network
termination.
To terminate the RediSTATION, install a 121 ohm 1% metal film
resistor between the CAN_High and CAN_Low terminals on the
DeviceNet terminal block.
1
2345678910
OFF = 0
ON = 1
Output Flash Rate 0 = 1 Hz (0.5 sec, On, 0.5 sec Off)
1 = 2 Hz (0.25 sec On, 0.25 sec Off)
DeviceNet Removable
Terminal Block
CAN_Low
CAN_High
Vista de pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 63 64

Comentarios a estos manuales

Sin comentarios