A-2 Specifications
Environment
Communications
Certifications
Ambient Temperature
Operating Temperature
0 to 55
° C (32 to 131° F)
Storage
-40 to 85
° C (-40 to 185° F)
Relative Humidity (non-condensing) 5 to 95%
50% max at 40° C (104° F)
Shock and Vibration
Shock (operating) 30G
Impulse Shock (non-operating) 50G
Vibration (operating) 2.5G at 58 to 2000 Hz
5 to 57 Hz 0.38mm displacement
(peak-to-peak)
Vibration (non-operating) 5.0G at 58 to 2000 Hz
5 to 57 Hz 0.76mm displacement
(peak-to-peak)
DeviceNet
Data Rates 125K, 250K, 500K BPS
Maximum Distance 500 meters (1600 feet) @125K
200 meters (600 feet) @250K
100 meters (300 feet) @500K
LED Indicator (Mod/Net Status) Operating Status (Green/Red)
2705-T3DN1B42A (conduit entry) UL Listed for Hazardous Location A196
Approved for Class I, Groups A, B, C, D,
Division 2, C-UL
2705-T3DN1A42A (sealed connector) UL Listed A191, C-UL