Publication 2705-UM001A-EN-P
B-6 DeviceNet Information
Instance 2 Attributes (Polled I/O Message)
1
xxxxxx = node address
Attribute
ID
Access
Rule
Name DeviceNet
Data Type
Data Value
1 Get State USINT 0 = nonexistent
1 = configuring
3 = established
4 = timed out
2 Get Instance Type USINT 1 = I/O message
3 Get Transport Class Trigger USINT 82
hex
4 Get Produced Connection ID UINT
01111xxxxxx
binary
1
5 Get Consumed Connection ID UINT
10xxxxxx101
binary
1
6 Get Initial Comm
Characteristics
USINT 01
hex
7 Get Produced
Connection Size
UINT 1
8 Get Consumed
Connection Size
UINT 1
9 Get/Set Expected Packet Rate UINT 0 msec (default),
with time resolution
of 10 msec
12 Get/Set Watchdog Timeout Action USINT 0 = timeout (default)
1 = auto delete
2 = auto reset
13 Get Produced Connection
Path Length
UINT 6
14 Get Produced Connection Path
Logical Segment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Structure of:
USINT
USINT
USINT
USINT
USINT
USINT
20
hex
04
hex
24
hex
01
hex
30
hex
03
hex
15 Get Consumed Connection
Path Length
UINT 6
16 Get Consumed Connection Path
Logical Segment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Structure of:
USINT
USINT
USINT
USINT
USINT
USINT
20
hex
04
hex
24
hex
02
hex
30
hex
03
hex