Rockwell-automation 2705 RediSTATION Operator Interface User Manual Manual de usuario Pagina 30

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 29
Publication 2705-UM001A-EN-P
3-4 Operations
DeviceNet Operations
The Allen-Bradley 1747-SDN and 1771-SDN DeviceNet Scanner
Modules are master devices on the DeviceNet network. The
RediSTATION supports the Master/Slave Connection Set for master/
slave communications on the DeviceNet network.
To communicate with a RediSTATION, the DeviceNet Scanner Module
must be configured with the RediSTATION:
node address
input bytes (1)
output bytes (1)
The DeviceNet Scanner Module:
connects to the RediSTATION slave device
performs the appropriate connection configuration
polls the RediSTATION for inputs and outputs
Response Times
The RediSTATION responds to a DeviceNet Scanner poll within 1
millisecond.
The switch inputs are debounced for 50 milliseconds. When a change
of state is detected, the inputs are not read for another 50 milliseconds
Vista de pagina 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 63 64

Comentarios a estos manuales

Sin comentarios