Constructing the Transfer PathA–2
The format of the transfer path on remote DH+ networks is:
Transfer Path Format Valid Entries
ll.rrr.ss
ll local KA address
rrr remote KA address
ss PanelView address on remote DH+
0 – 77 (octal)
0 – 376 (octal)
0 – 77 (octal)
or
You can shorten the offlink address by combining the remote KA address and remote
transfer path into one three-digit number. The system reads only the first digit of the remote
KA address, and adds the two-digit remote PanelView address to produce a shorter
address.
ll.rss
ll local bridge address
rss combined remote KA address and remote PanelView
address
0 – 77 (octal)
0 – 376 (octal)
The following figure shows a development computer connected to a
DH+ network. The local DH+ network is bridged to a remote DH
network, which is bridged to a second remote DH+ network. The
1785-KA interface modules are used to bridge the networks.
DH+ Networks Bridged by
a 1785-KA