Rockwell-automation 5730 DriveLogix5730 Controller for PowerFlex 700S Manual de usuario Pagina 107

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 217
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 106
Communicating with Devices on an EtherNet/IP Link 6-3
Assigning Network Parameters with BOOTP/DHCP
The EtherNet/IP Option board ships with BOOTP enabled. You must assign
an IP address to the Ethernet port in order for the controller to communicate
over an EtherNet/IP network.
The BOOTP/DHCP utility is a stand alone program that is located in the:
BOOTP-DHCP Server folder in the Rockwell Software program folder
on the Start menu (the utility is automatically installed when you install
RSLinx software)
Tools directory on the RSLogix 5000 installation CD.
The computer running the BOOTP/DHCP utility and the DriveLogix5730
controller must be on the same EtherNet/IP network.
To use the BOOTP/DHCP utility:
ahw0861.tif
1. Start the BOOTP/DHCP software.
2. From the Tools menu, select Network Settings.
ahw0858.tif
Click OK.
3. Enter the required data.
Note: If you have not run the BOOTP/DHCP program before,
it will automatically launch the Network Settings window.
Vista de pagina 106
1 2 ... 102 103 104 105 106 107 108 109 110 111 112 ... 216 217

Comentarios a estos manuales

Sin comentarios