6-30 Communicating with Devices on an EtherNet/IP Link
Using Ladder Logic to Dynamically Configure Messages
Use ADD instructions to calculate the MSG Source Length.
0xFF 0x0100 Error returned by email server; check the Destination string for reason. The email message
was not queued for delivery.
0x0101 SMTP mail server not configured. Attribute 5 was not set with a SMTP server address.
0x0102 “To:” address not specified. Attribute 1 was not set with a “To:” address AND there is not a
“To:” field header in the email body.
0x0103 “From:” address not specified. Attribute 2 was not set with a “From:” address AND there is not
a “From:” field header in the email body.
0x0104 Unable to connect to SMTP mail server set in Attribute 5. If the mail server address is a
hostname, make sure that the device supports DNS, and that a Name Server is configured. If
the hostname is not fully qualified, i.e., “mailhost” and not “mailhost.xx.yy.com” then the
domain must be configured as “xx.yy.com”. Try “ping <mail server address>” to insure the mail
server is reachable from your network. Also try “telnet <mail server address> 25” which
attempts to initiate a SMTP session with the mail server via telnet over port 25. (If you connect
then enter “QUIT”).
0x0105 Communication error with SMTP mail server. An error occurred after the initial connection with
the SMTP mail server.
See the ASCII text following the error code for more details as to the type of error.
0x0106 SMTP mail server host name DNS query did not complete. A previous send service request
with a host name as the SMTP mail server address did not yet complete. Note that a timeout
for a DNS lookup with an invalid host name can take up to 3 minutes. Long timeouts can also
occur if a domain name or name server is not configured correctly.