Placing and Configuring the Drive 2-17
Configuring the Drive’s Response to a Connection Failure or Controller
Mode Change
The drive contains several parameters that allow you to configure the drive’s
response to communication loss to the controller. From the drive’s
perspective, a communication loss can come in the following two forms.
The controller closes the connection (for example, the connection is
inhibited).
A general failure occurs causing the connection to time out.
Parameter 386 [Lgx OutofRunCnfg] configures the drive’s response to the
controller is removed from the Run Mode. Parameter 387 [Lgx Timeout
2. To send additional data from the drive to the controller, go to the To DriveLogix tab.
Click the button in front of the
UserDefinedRealData[0] tag
ahw0790.tif
ahw0791.tif
3. Select the desired source (parameter 307 [Output Voltage] in this example) in the resulting window.