29Installation
Power input
Connect the AC line power leads to terminals L1 and L2 as
shown in Figure 8 (page 31). Ensure that earth ground is
connected to the green screw inside the case.
Field output
ATTENTION: Do not make any connections to F1 and
F2 when using a permanent magnet motor.The field
output is for shunt wound motors only. See Table 3 for
field output connections.
Table 3. Field Output Connections
Line Voltage Approximate Connect Motor Terminal
(VAC) Field Voltage (VDC) Field To Numbers
115 50 F1 and L1 4 and 1
115 100 F1 and F2 4 and 5
230 100 F1 and L1 4 and 1
230 200 F1 and F2 4 and 5