Rockwell-automation Ethernet Design Considerations Reference Manual Manual de usuario Pagina 68

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 67
68 Rockwell Automation Publication ENET-RM002C-EN-P - May 2013
Chapter 4 EtherNet/IP Protocol
Table 14 - Additional ControlLogix EtherNet/IP Communication Module Specifications
Cat. No. Series Firmware
Revision
RSLogix 5000
Software Version
RSLinx Software
Version
Packet Rate Capacity (packets/ second)
(2)
Support for
Extended
Environment
(4)
Integrated Motion
on the EtherNet/IP
Network Axes
I/O HMI/MSG
1756-ENBT Any Any 8.02.00 or later 2.30 or later 5000 900 No N/A
1756-EN2F A 2.x 15.02.00 or later 2.51 or later 10,000 2000 No N/A
3.6 or later 18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
B Up to 8 axes
supported
(5)
1756-EN2T A 2.x or earlier 15.02.00 or later 2.51 or later 10,000 2000 No N/A
3.6 or later 18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
B2.x 15.02.00 or later 10,000 N/A
3.6 or later 18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
C Up to 8 axes
supported
(5)
1756-EN2TXT B 2.x 15.02.00 or later 2.51 or later 10,000 2000 Yes N/A
3.6 or later 18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
C Up to 8 axes
supported
(5)
1756-ENT2TR A 2.x 17.01.02 or later 2.55 or later 10,000 2000 No N/A
3.6 or later 18.02.00 or later
(1)
2.56 or later 25,000
(3)
Up to 4 axes
supported
(5)
B Up to 8 axes
supported
(5)
1756-EN2TRXT A 5.028 or later 20.01.00 or later 2.56 or later 25,000
(3)
2000 Yes N/A
1756-EN2TSC A 5.028 or later 20.01.00 or later 2.56 or later 25,000
(3)
930 with encryption
1800 without encryption
No N/A
1756-EN3TR A 3.6 or later 18.02.00 or later
(1)
2.56 or later 25,000
(3)
2000 No Up to 255 axes
supported
(5)
9300-ENA A 1.12 or later N/A N/A N/A No N/A
(1) This version is required to use CIP Sync technology, Integrated Motion on the EtherNet/IP Network, or Exact Match keying.
(2) For more information on Packet Rate Capacity, see Packets Rate Capacity
on page 69.
(3) The packet rate capacity can change slightly depending on the firmware revision of your EtherNet/IP communication module. For more information, see Packets Rate Capacity
on page 69.
(4) Module operates in a broad temperature spectrum, -20…70 ºC (-4…158 ºF), and meets ANSI/ISA-S71.04-1985 Class G1, G2 and G3, as well as cULus, Class 1 Div 2, C-Tick, CE, ATEX Zone 2 and SIL 2
requirements for increased protection against salts, corrosives, moisture/condensation, humidity, and fungal growth.
(5) This value assumes the use of a 1756-L7x ControlLogix controller. For a 1756-L6x ControlLogix controller, see ControlLogix Controllers User Manual, publication 1756-UM001
.
Vista de pagina 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 105 106

Comentarios a estos manuales

Sin comentarios