Rockwell Automation Publication ENET-RM002C-EN-P - May 2013 95
Predict System Performance Chapter 5
EtherNet/IP Modules Functioning as Adapters
EtherNet/IP modules 4…8 function as adapters.
Each EtherNet/IP module functioning as an adapter in an I/O chassis, that is,
1756-EN2T EtherNet/IP communication modules 4…8 in the example on
page 91
, has these connections:
One rack-optimized connection for digital I/O modules in its chassis.
The digital I/O has a required RPI = 20 ms
Three direct connections for analog I/O modules in its chassis.
The analog I/O has a required RPI of 50 ms.
1756-EN2T Module 4
1756-EN2T Module 7
1756-EN2T Module 5
1756-EN2T Module 8
1756-EN2T Module 6