Rockwell-automation Ethernet Design Considerations Reference Manual Manual de usuario Pagina 92

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 91
92 Rockwell Automation Publication ENET-RM002C-EN-P - May 2013
Chapter 5 Predict System Performance
Explicit Messaging
The RSView® and PanelView Plus messages are explicit messages. Reserve 10% of
the bandwidth of the EtherNet/IP communication module for explicit
messaging.
Explicit messaging throughput is also dependent upon network availability and
target availability. Therefore, reserving 10% of the total bandwidth does not
guarantee throughput.
Next determine if each EtherNet/IP communication module has enough
bandwidth to handle the implicit messaging.
EtherNet/IP
Interface
Total Bandwidth 10% Reserve for Explicit Messaging
1756-ENBT 5000 pps 500 pps
1756-EN2F
1756-EN2T
1756-EN2TR
1756-EN2TXT
1756-EN3TR
The pps for these modules depends on the
module’s series and firmware revision.
The modules support this pps:
Series A, firmware revision 2.x orearlier
= 10,000 pps
Series A or later, firmware revision 3.6 or
later= 25,000 pps
For more information on the pps supported
by these modules, see Table 12 on page 66
.
One of the following:
Series A, firmware revision 2.x or earlier
= 1000 pps
Series A or later, firmware revision 3.6 or
later= 2500 pps
1768-ENBT 5000 pps 500 pps
1769-L23Ex 2000 pps 200 pps
1769-L32E
1769-L35E
4000 pps 400 pps
1769-L30ER 6000 pps 600 pps
1769-L30ERM
1769-L30ER-NSE
1769-L33ER
1769-L33ERM
1769-L36ERM
1769-L24ER-QB1B
1769-L24ER-QBFC1B
1769-L27ERM-QBFC1B
1769-L16ER-BB1B
1769-L18ER-BB1B
1769-L18ERM-BB1B
1788-ENBT 5000 pps 500 pps
1734-AENT 5000 pps 500 pps
1794-AENT 9500 pps 950 pps
Vista de pagina 91