Rockwell-automation Ethernet Design Considerations Reference Manual Manual de usuario Pagina 89

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 88
Rockwell Automation Publication ENET-RM002C-EN-P - May 2013 89
Predict System Performance Chapter 5
Estimate Maximum Input or Output Times for CIP Connections
System response is dependent on several factors. These are the dominant factors:
RPI value
Number of implicit CIP connections.
To simplify, the response time of a connection can be approximated with only
the RPI.
The maximum input (I/O to controller) or output (controller to I/O) times for
implicit CIP connections can be estimated as follows:
Rack-optimized: 1 RPI
Direct Connect:
Digital = 1 RPI
Analog (nonisolated) = 2 RTS (Real Time Sampling rate)
Analog (isolated) = 1 RTS
Produced/Consumed Tag = 1 RPI
The above response times are estimates. For more accurate numbers, include
system delays, as described in Refine Estimates
on page 99.
Vista de pagina 88
1 2 ... 84 85 86 87 88 89 90 91 92 93 94 ... 105 106

Comentarios a estos manuales

Sin comentarios