Rockwell Automation Publication ENET-RM002C-EN-P - May 2013 91
Predict System Performance Chapter 5
Determine If System Has Sufficient Bandwidth
to Meet Application Requirements
Based on the system requirements, the initial network diagram is shown below:
Chassis 1
1756-L73 Controller
1756-EN2T Module 1
One Produced Tag
PanelView Plus Terminal
Workstation
with RSView
To Company
Intranet
Chassis 4
1756-EN2T Module 4
Three Analog I/O Modules
Three Digital I/O Modules
Chassis 7
1756-EN2T Module 7
Three Analog I/O Modules
Three Digital I/O Modules
Chassis 5
1756-EN2T Module 5
Three Analog I/O Modules
Three Digital I/O Modules
Chassis 8
1756-EN2T Module 8
Three Analog I/O Modules
Three Digital I/O Modules
Chassis 6
1756-EN2T Module 6
Three Analog I/O Modules
Three Digital I/O Modules
IMPORTANT: Each chassis with three analog and three digital I/O modules, that is, chassis 4…8, uses these connections:
Three direct connections (one for each analog I/O module in the chassis)
One rack connection (one for all digital I/O modules in the chassis)
Switch
Chassis 2
1756-L73 Controller
1756-EN2T Module 2
One Consumed Tag
Chassis 3
1756-L73 Controller
1756-EN2T Module 3
One Consumed Tag