
Publication 1394-5.0 — May 2000
8-10 Configuring Your 1394 Analog Servo System
[Disp-D/A Monitor]
This parameter quickly establishes links to the
D/A test points. It will link the selected axis [Iq
Cur Ref] to test point 1, and the [Vel Feedback]
to test point 2. It will also link the [Vel Feedback]
to all the SCANport analog display parameters.
Parameter Numbers 20
Parameter Group Setup
Display Units None
Parameter Type Read/Write
Change While Running No
Linkable No
Default Value 0"Axis 0"
Selections 0"Axis 0"
1"Axis 1"
2"Axis 2"
3"Axis 3"
4 "Not Linked"
[Drive OK Mode]
This parameter selects operation of the Drive OK
relay. (DROK)
Parameter Numbers 19
Parameter Group Setup
Display Units None
Parameter Type Read/Write
Change While Running Ye s
Linkable No
Default Value 0 "Fault Only"
Selections 0 "Fault Only"active fault opens DROK relay.
1 "Fault and UVlt"active fault or bus undervoltage opens DROK
relay.
Comentarios a estos manuales