Rockwell Automation Publication 1734-UM018B-EN-P - October 2013 29
Chapter
4
Configure the Adapter for Direct Connection
in RSLogix 5000 Software
Overview
In this example, a ControlLogix controller communicates with I/O modules via
the adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the
data. The modules presented in this chapter use RSLogix 5000 software,
revision 17 and above.
Topic Page
Set Up the Hardware 30
Create the Example Application 31
Configure the I/O Modules 32
Add the Local EtherNet/IP Bridge to the I/O Configuration 32
Add the POINT I/O Adapter to the I/O Configuration 35
Add the POINT I/O Modules to the I/O Configuration 38
Edit the Controller Tags 43
Create the Ladder Program 44
Download the Program to the Controller 44
Verify the Module Chassis Size 45
Configure the Adapter with Fixed IP Address 48
Recover From an Overloaded Adapter 49
Chapter Summary 50
ATTENTION: You must only use Series C and above POINT I/O modules
with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O
modules do not work with 1734-AENT EtherNet/IP Adapters (does not
apply to POINTGuard modules).