42 Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
4. Enter values for Name and Slot, noting that we used the following values.
5. Choose the Connection tab to set the RPI value.
The RPI is selectable since it is a direct connection.
6. Enter 10 ms as the RPI for the 1734-OV4E module to set how often you
exchange data with the I/O adapter.
7. Click OK to save the configuration.
The module appears in the I/O configuration folder indented under
Ethernet.
Name POINT_Digital_Output
Slot 2
IMPORTANT
To avoid overloading the I/O adapters, we recommend that RPI be no
less than 10 ms for rack connections and 50 ms for direct
connections.