Rockwell Automation Publication 1734-UM018B-EN-P - October 2013 51
Chapter
5
Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software
Overview
This chapter guides you through the steps required to configure your AENT
adapter with both direct and rack-optimized I/O connections using
RSLogix 5000 software.
You can mix I/O connection formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter.
I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimized I/O connection has no bearing on the direct
I/O connections. The modules presented in this chapter have a configuration
using RSLogix 5000 software, revision 11. The chapter contains the following
main sections
.
Topic Page
Set Up the Hardware 52
Create the Example Application 53
Configure the I/O Modules 54
Add the Local EtherNet/IP Bridge to the I/O Configuration 54
Add the POINT I/O Adapter to the I/O Configuration 57
Add the POINT I/O Modules and Configure for Rack-optimized Connection 61
Add the POINT I/O Module and Configure For Direct Connection 63
Download the Program to the Controller 66
Verify the Module Chassis Size 67
Access Module Data 69
Chapter Summary 70
ATTENTION: You must only use Series C and above POINT I/O modules
with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O
modules do not work with 1734-AENT EtherNet/IP Adapters (does not
apply to POINTGuard modules).