44 Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Create the Ladder Program
Create the example ladder program to test the I/O.
1. Under the Main Program folder, double-click Main Routine.
2. Enter the following ladder program using the tags previously created.
3. Save the program.
Download the Program to
the Controller
Follow this procedure to download the program you just saved to the
ControlLogix controller.
1. From the main menu, choose Communications>Who-Active.
The Who Active dialog opens.
2. Navigate to select the slot where the controller is located in the chassis.
3. Choose Set Project Path.