36 Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
3. Select your adapter from the list and click Create.
The New Module dialog opens.
4. Select the General Tab and enter the module details, noting that we used
the following values.
5. Click Change...
The Module Definition dialog opens.
6. Choose values for Series, Revision, Electronic Keying, Connection, and
Chassis Size, noting that we used the following values:
Name POINT IO Adapter
IP Address 10.88.70.2
IMPORTANT
Note that the slot field is disabled because the slot is automatically 0
for the 1734-AENT/B adapter.
Series B
Connection None
Chassis Size 5
Electronic Keying Compatible Module
Revision 4.3