56 Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
5. Enter values for Name, IP Address, and Slot, noting that we used the
following values:
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking
the Change button. Some of the properties cannot be modified while
pending edits exists.
To change the default module properties,
6. Click Change...
The Module Definition dialog opens.
7. Enter or select values for Series, Revision, Electronic Keying, Rack
Connection, and Time Sync Connection, noting that we used the
following values:
8. Click OK to accept the configuration.
The module appears indented under under the I/O Configuration folder.
Name Local_ENBT
IP Address 10.88.70.4
Slot 3
Series A
Revision 5.1
Electronic Keying Compatible Module
Rack Connection None
Time Sync Connection None