Using High-Speed Counter Instructions
12–9
When
a high preset is reached, no counts are lost.
Hardware and instruction accumulators are reset.
Instruction high preset is loaded to the hardware high preset.
If the DN bit is not set, the DN bit is set. The IH bit is also set and the IL, IV,
and IN bits are reset.
If the DN bit is already set, the OV bit is set. The IV bit is also set and the IL,
IV and IN bits are reset.
High-speed counter interrupt file (program file 4) is executed if the interrupt is
enabled.
The following tables summarize what the input state must be for the corresponding
high-speed counter action to occur:
Up Counter
Input State
H g -Speed
Input Count
(I/O)
Input
Direction
(I/1)
Input Reset
(I/2)
Input Hold
(I/3)
HSC Rung
High-Speed
Counter Action
Turning
Off-to-On
NA NA NA True Count Up
NA NA NA NA False Hold Count
Off, On, or
Turning Off
NA
Off, On, or
Turning Off
NA NA Hold Count
NA (Not Applicable)