Wiring
Y
our Controller
2–23
Analog
V
oltage and Current Input and Output Ranges
Analog Voltage Input Range
Operating
Range
Overrange
Underrange
–10.5V dc 10.5V dc
–24V dc
24V dc
Analog Current Input Range
Operating
Range
Overrange
Underrange
–21 mA 21 mA
–50 mA 50 mA
Note The
analog voltage inputs ar
e pr
otected to withstand the application of 24V dc
without damage to the contr
oller
. The analog curr
ent inputs ar
e pr
otected to
withstand the application of 50 mA without damage.
Analog Voltage Output Range
Operating
Range
0V dc 10V dc
Analog Current Output Range
Operating
Range
20 mA
4 mA
Note The
analog outputs ar
e pr
otected to withstand the short cir
cuiting of the voltage or
curr
ent outputs without damage to the contr
oller.
For information on analog signal and data word values using the nominal
transfer function formula, see page 5–5.