Preface
MicroLogix 1000 Programmable Controllers User Manual
A–8
Response Times for dc Inputs 4 and Above (applies to 1761-L10BWA, 1761-L16BWA,
-L20BWA-5A, -L32BWA, -L10BWB, -L16BWB, -L20BWB-5A, -L32BWB, -L16BBB, and
-L32BBB controllers)
Nominal Filter
Setting (ms)
Maximum ON
Delay (ms)
Maximum OFF
Delay (ms)
0.50 0.500 0.500
1.00 1.00 1.000
2.00 2.000 2.000
4.00 4.000 4.000
8.00
➀
8.000 8.000
16.00 16.000 16.000
➀
This is the default setting.
Response Times for ac Inputs (applies to 1761-L16AWA, -L20AWA-5A, -L32AWA, and
-L32AAA controllers)
Nominal Filter
Setting (ms)
➀
Maximum ON
Delay (ms)
Maximum OFF
Delay (ms)
8.0 20.0 20.0
➀
There is only one filter setting available for the ac inputs. If you make another selection the
controller changes it to the ac setting and sets the input filter modified bit (S:5/13).