Preface
MicroLogix 1000 Programmable Controllers User Manual
12–26
Example 1
To enter the REM Run mode and have the HSC Outputs, ACC, and Interrupt
Subroutine resume their previous state, apply the following:
(Rung 2:0)
No action required. (Remember that all OUT instructions are zeroed
when entering the REM Run mode. Use SET/RST instructions in place of
OUT instructions in your conditional logic requiring retention.)
| S:1 +HSL–––––––––––––––+ |
|––][–––––––––––––––––––––––––––––––––––+HSC LOAD +–|
| 15 |Counter C5:0| |
| |Source N7:0| |
| |Length 5| |
| +––––––––––––––––––+ |
Rung 2:1
| +HSC––––––––––––––––––––+ |
|–––––––––––––––––––––––––––––+HIGH SPEED COUNTER +–(CU)–|
| |Type Encoder(Res,Hld) +–(CD) |
| |Counter C5:0+–(DN) |
| |High Preset 1000| |
| |Accum 0| |
| +–––––––––––––––––––––––+ |