Connecting CompactLogix Controllers on Ethernet 8-19
Download to the
CompactLogix Controller
Through a ENI/ENIW
Series B/C/D via Ethernet
In order to download your programs to the CompactLogix controller
directly through the ENI/ENIW series B/C/D to the SLC 5/05 controller
and to the ControlLogix controller via Ethernet, you must configure an
Ethernet driver in RSLinx.
Follow these steps to configure RSLinx for Ethernet operation.
1. Open RSLinx and open the driver configuration dialog.
2. The “Configure Dialog” will open, select Ethernet devices from
the available drivers, and then click “OK” to load the driver into
RSLinx.
Once the Ethernet driver is loaded, either highlight and select
“Configure” or simply double click on the Ethernet driver.
IMPORTANT
You must use RSLinx version 2.31.00 or newer to
browse with the 1761-NET-ENI/1761-NET-ENIW
series B/C/D via Ethernet to a CompactLogix
controller.