Rockwell-automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) Manual de usuario Pagina 127

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 126
1 Publication 1761-UM006E-EN-P - August 2005
Appendix
A
Specifications
Physical Specifications
Series C and D Ethernet
Specifications
Communication Rate: Auto-negotiates 10 Mbps, full- or half-duplex
and 100 Mbps, full- or half-duplex
Connector: 10/100-Base-T
MicroLogix Web Site
Visit http://www.ab.com/micrologix for more information on
MicroLogix products. You can find a variety of application information
and White Papers covering specific technical topics.
Description ENI/ENIW Specification
24V dc Power Source Requirement 20.4 to 26.4V dc
24V dc Current Draw 50 mA typical, 100 mA maximum
Maximum Inrush Current 200 mA
Internal Isolation 710V dc for one minute
Vibration operating: 10 to 500 Hz, 5.0g, 0.030 in. peak-to-peak, 2 hour each axis
Shock operating: 30g, ±3 times each axis
non-operating: 35g (DIN Rail Mount) 50g (Panel Mount), ±3 times each axis
Operating Ambient Temperature 0° C to +60° C (+32° F to +140° F)
Storage Temperature -40° C to +85° C (-40° F to +185° F)
Humidity 5% to 95% relative humidity (non-condensing)
Agency Certification
(1)
UL 1604
C-UL C22.2 No. 213
Class I Division 2 Groups A,B,C,D
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Radiated and Conducted Emissions: EN 50081-2, Class A
The module has passed testing at the following levels:
ESD Immunity (EN 61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (EN 61000-4-3) 10V/m, 80 to 1000 MHz, 80% amplitude modulation, and 900 MHz keyed carrier
Fast Transient Burst (EN 61000-4-4) Power supply: 2 kV, 5 kHz
RS-232 and Ethernet: 1kV, 5 kHz
Surge Immunity (EN 61000-4-5) Power Supply: 500V
Ethernet (unshielded cable): 2 kV
RS-232 and Ethernet (shielded cable): 1 kV galvanic gun
Conducted Immunity (EN 61000-4-6) Power Supply: 10V, 0.15 to 80 MHz
RS-232 and Ethernet (unshielded cable): 3V, 0.15 to 80 MHz
RS-232 and Ethernet (shielded cable): 10V, 0.15 to 80 MHz
(1) Shielded Ethernet cable required for marine certification.