
Output Override and I/O Update Instructions
Chapter 7
717
Table 7.C
Average
Execution Times in Microseconds for FILET
OFILE AND, OR,
XOR Instructions when Instruction is T
rue
Rate Per Scan Dist. Complete Mode Complete Mode
5
10
15
25
50
100
256
512
174
223
272
370
615
1105
2648
5171
148
197
246
344
589
1079
2622
5145
Formula for more exact approximations can be found in Section C.6.
Execution Time for incremental mode is 100 microseconds per scan.
When FALSE, execution time is 17.6 microseconds.
Table 7.D
The
Following Instructions Reset the W
atchdog T
imer
FileToFile Move
WordToFile Move
FileToWord Move
FileToFile AND, OR, XOR
WordToFile AND, OR, XOR
File Complement
File Search
File Diagnostic
Return
End
T.End
SBR
Sequencer In
Sequencer Out
Sequencer Load
Fifo Load
Fifo Unload
Shift File Up
Shift File Down
Shift Bit Left
Shift Bit Right
Block Transfer (for processors equipped with cat. no. 1772LG, processor module, Rev. J firmware
or later)
Comentarios a estos manuales