Rockwell-automation 1772-LP3 PLC - 2/30 Programmable Controller Progra Manual de usuario Pagina 263

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 346
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 262
Bit Shifts
Chapter 14
1411
Instruction overview:
Output instruction
3 words of users program required
Key sequence: [SHIFT REG] 17
To program a Reset Shift Bit instruction press [SHIFT REG] 17. A display
represented by Figure 14.10 will appear.
Figure 14.10
RESET
SHIFT BIT Format
RESET SHIFT BIT
FILE: 110
BIT NO.: 001
Numbers
shown are default values. Bold numbers must be replaced by userentered values. The number of default address digits
initially displayed  3, 4, or 5  will depend on the size of the data table. Initially displayed default values are governed by the I/O rack
configuration.
FILE :
Starting address of the file (file of bit shift instruction).
BIT NUMBER
:
Decimal number of the bit to be set (1999).
Figure 14.11 shows the format of Figure 14.10 for the following condition
of the bit shift register of Figure 14.1.
File – The file starts at word 400
8
.
Bit No. – Turn bit number 67 in shift register (Figure 14.1) to off (0).
Figure 14.11
RESET
SHIFT BIT Example Rung
RESET SHIFT BIT
FILE: 400
BIT NO.: 067
14.6.1
Programming Reset Shift Bit
Instruction
Vista de pagina 262