Addressing
Appendix A
A6
Using 16Point I/O Modules
High-Density (16-point) I/O modules provide 16 input terminals or 16
output terminals. 16-point I/O modules use a full word in the input or
output image table. Two 16-point modules (one input and one output) can
be used in a 2-slot I/O group (Figure A.4).
Figure A.4
Illustration
of 2slot Addressing with 16point Input and Output Modules
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
Input
Terminals
Output
Terminals
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Output
image table word corresponding
to the I/O group (all bits used).
Input image table word corresponding
to the I/O group (all bits used).
2slot
I/O Group
NOTE:
16point input and output
modules use two words (one input,
one output) of the image table.
Because these modules use a full word in the image table, the only type of
module you can use in a 2-slot I/O group with a 16-point module is one