Message Formats
Appendix A
A4
Figure A.2
A RS-232-C Link Configuration that includes a line monitor
10069-I
1775KA
PLC3 Communication
Adapter Module
Toggle Switch
Industrial Terminal System
(Cat. No. 1770T4)
Channel B
Usersupplied 25 Pin
Male Connector with
Straight Hood
(Cat. No. 1770XXP)
RS232Device
25 Pin, Female
RS232C Connector
25 Pin, Male
RS232C Connector
25 Pin, Male
RS232C Connector
To program the industrial terminal to act as a line monitor, complete the
following steps:
1. Attach the 1770–KDA programming keyboard to the industrial
terminal.
2. Press SHIFT MODE and type 2 to select the alphanumeric mode.
In the steps that follow, you type a letter key repeatedly until the selection
you want appears on screen.
3. Type A to select the baud rate you are currently using on the line.
4. Type B to select no parity.
5. Type C to select 1 stop bit.
6. Type E to select cursor on.
7. Type F to select full–duplex.