Message Formats
Appendix A
A20
Where the extended status byte is optional.
A PLC–3 receives privileged commands from an RS–232–C device (such
as a computer); the PLC–3 does not send these commands. The
privileged commands are:
privileged read download request
privileged write upload request
diagnostic counters reset restart request
diagnostic loop set ENQs
diagnostic read set NAKs
diagnostic status set timeout
Privileged Read
Use this read command with a PLC–3 physical address as a starting
address. You use this command to upload from a PLC–3 to a computer.
The destination 1775–KA module will accept this command only after the
source station has successfully transmitted a shutdown request. The
function code for this command is 9.
Command Format:
DLE
SRC C
0
S
TNS
MD
F
TS
TNS
STX
FNC
09
SIZE
DST
DLE ETX
BCC
PLC-3
physical address
Reply Format:
TDATA–Max of 238 bytes or 119 words DLE ETX BCChis is the same
as the reply packet format for all reads.
A. Format when the command was successfully executed
DLE
C
S
TNS
MD
TS
TNS
STX
DLE ETX
BCC
DATA - Max of 244 bytes or 122 words
DST
SRC
4F
B. Format when reporting an error
DLE
SRC
STX DST C
4F
S
TNS
MD
TS
TNS
DLE ETX
BCC
ETX
ST S
Where the extended status byte is optional.
Privileged Commands