Publication 1797-6.5.3 - March 2006
B-8 FLEX Ex HART Module Commands
Command 132
Write Static Data of Transmitters command is set when a preamble length
outside of the range 5 to 20 is set to 5 or 20. When written, the data of
command 132 also invokes the functionality of command 133 (Remove
instrument from list) internally. There are no response data bytes.
Command 133
The Delete Transmitters From the Transmitter List command removes
transmitters with the given long frame address from the transmitter list and the
SCAN list. No more than 34 instruments may be requested.
Table B.7 Command 132 Request Data Bytes
Byte Description
0…4 EXT_ADDR_0
Extended address of instrument 0
(1)
(1)
0, if it is attended to project no instrument.
EXT_ADDR_I Extended address of instrument 1
……
Command-specific Response Codes
5 Error Too few data bytes received
16 Error Access restricted
32 Error Busy
Table B.8 Command 133 Request and Response Data Bytes
Byte Description Value
Request Data Bytes
0…4 EXT_ADDR_0 Extended address of instrument 0
5 COUNT_0 Bytes before next item
EXT_ADDR_I Extended address of instrument I
COUNT_I Bytes before next item
Response Data Bytes
0…4 EXT_ADDR_0 Extended address of instrument 0
5 COUNT_0 Bytes before next item
6 ERROR_0 Error 0 0 = Instrument
present.
64 = Unknown
instrument.