Publication 1797-6.5.3 - March 2006
D-4 Configure the 1797-OE8H Module in RSLogix 5000 Software Over the ControlNet Network
Analog Fault State
Fault Mode
Local Fault Mode
The Local Fault mode uses bit [Adapter Name]:[Slot]:C.Data[0].15.
Analog Fault State Value for
Channel
Bits
0 [Adapter Name]:[Slot]:C.Data[3]
1 [Adapter Name]:[Slot]:C.Data[4]
2 [Adapter Name]:[Slot]:C.Data[5]
3 [Adapter Name]:[Slot]:C.Data[6]
4 [Adapter Name]:[Slot]:C.Data[7]
5 [Adapter Name]:[Slot]:C.Data[8]
6 [Adapter Name]:[Slot]:C.Data[9]
7 [Adapter Name]:[Slot]:C.Data[10]
Bits 9 or 11 Bits 8 or 10
Min Value of Data Range 0 0
Max Value of Data Range 0 1
Hold Last State 1 0
Analog Fault State Value 1 1
Channel Bits
0 and 1 [Adapter Name]:[Slot]:C.Data[0].12
2 and 3 [Adapter Name]:[Slot]:C.Data[0].13
4 and 5 [Adapter Name]:[Slot]:C.Data[1].12
6 and 7 [Adapter Name]:[Slot]:C.Data[1].13
Disabled 0
Enabled 1
Communications Fault 0
Any Fault 1