Publication 1797-6.5.3 - March 2006
D-8 Configure the 1797-OE8H Module in RSLogix 5000 Software Over the ControlNet Network
Input
Refer to the following tables for input information.
Diagnostic Status Data
HART Rebuild Bit
The HART rebuild bit is [Adapter Name]:[Slot].I.Data[0].7.
Fault Alarm
Bit 3 Bit 2 Bit 1 Bit 0
Normal 0000
Calibration Failure 0001
Configuration Failure0010
Message Failure 0011
Lead Break Detection 0100
EEPROM Failure 0101
RAM Failure 0101
ROM Failure 0111
Calculation Failure 1000
Data Out of Range 1011
Channel Bits
0 [Adapter Name]:[Slot]:I.Data[0].8
1 [Adapter Name]:[Slot]:I.Data[0].9
2 [Adapter Name]:[Slot]:I.Data[0].10
3 [Adapter Name]:[Slot]:I.Data[0].11
4 [Adapter Name]:[Slot]:I.Data[0].12
5 [Adapter Name]:[Slot]:I.Data[0].13
6 [Adapter Name]:[Slot]:I.Data[0].14
7 [Adapter Name]:[Slot]:I.Data[0].15