1-4 About the FLEX Ex HART Analog Modules
Data Format Alarm Example
In this example, the normal active data range is 4 to 20 mA. The alarms are
generated in three overlapping bands.
Overrange Alarm
The Overrange alarm notifies you when module input is overrange. When the
input signal exceeds 100% (20 mA), an Overrange Alarm is generated.
This alarm stays active at any value above 100% of range and is always enabled
by the module.
Underrange Alarm
The Underrange alarm works in a fashion converse to the overrange. This
feature notifies you when the input signal falls underrange. If the input signal
falls below 0% (4 mA), an Underrange Alarm is generated.
This alarm stays active at any value below 0% of range and is always enabled by
the module.
PHYSICAL INPUT SIGNAL RANGE
0 mA 4 mA 20 mA 22 mA
Remote Fault Remote Fault
Local
Fault
Local
Fault
Underrange Overrange
Programmable
in 20 0.1 mA
Steps by Error
Level 0.1 mA
Steps
Parameter
-12.50%
0.00%
-25.00%
Remote Transmitter Error
Up/Down Parameter
Determines Which of These
is Active
Programmable
in 20 0.1 mA
Steps by Error
Level 0.1 mA
Steps
Parameter
100.00% 112.50%